Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | 17.06 | November 2024 | Enhancement | Added XL10W prime support. | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | 17.06 | November 2024 | Enhancement | Added new blocks STRINGTOUARRAY and UARRAYTOSTRING in Enhanced IEC to support USINT data types.
Note: This requires Cscape 10 SP1 onwards. | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | 17.06 | November 2024 | Enhancement | The following enhancements have been added to MQTT Sparkplug:
• Increased store-and-forward queue length from 256 to 1024
• Increased maximum publish topic size to 256 and 128 metrics per topic
• Added Auto Reconnect enable/disable with configurable timeout
• Added the ability to choose if a metric should be buffered or not in a store-and-forward situation | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | 17.06 | November 2024 | Bug Fix | Resolved: Following a firmware update, the netmask changed to 0.0.0.0 instead of 255.255.255.0
Note
• When the netmask is entered as 0.0.0.0 from the System Menu, it is automatically changed to 255.255.255.0.
• When the user downloads a program with netmask 0.0.0.0, the device displays 255.255.255.0 after download. | |
Prime XL15 | CSCAN 17.04 | September 2024 | Bug Fix | Resolved: USB Type C communication not working on XL15 Prime model. | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Enhancement | Retain variable support added for variable-based advanced ladder
Note: This requires Cscape version 10 onwards | |
Prime XL15 only | CSCAN 17.02 | August 2024 | Enhancement | Added support to XL15 Prime model | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Fixed UTC time not updating when downloaded from Cscape using IEC or Enhanced IEC language | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved issue wherein CV value of a PID block was not getting updated when configured in Enhanced IEC program | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved: Adjacent status register was being affected when the first status register was updated in the Removable Media copy and delete blocks | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | • Resolved: NTP was not working when configured with IP address
• Resolved: NTP server was skipping a day on new year’s if it was a leap year | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved: Performance of the device slows down and scan rate increases at higher temperatures | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved: RTC time was being incremented by one (1) hour per power cycle when Daylight Savings Time was enabled | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved: In read, the RM block was reading entire elements / data for an ASCII data type instead of reading only the configured number of elements | |
Prime X5, XL4, XL6, XLW, XL7, XL10, XL15 | CSCAN 17.02 | August 2024 | Bug Fix | Resolved: Protocol size was displayed as +++++++ for BACNet MSTP server in System Menu > View Status | |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Enhancement | Added build version and firmware version in system menu | view status. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Enhancement | Added limitations for Enhanced IEC Removable media Write and Read blocks to resolve the screen calibration being corrupted / system exception was being obtained when data was being written beyond 128 words (%M2048) using write removable media block | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Added support for using external modem as client with modem blocks. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved MAC ID was not being displayed in LAN2 when USB to ethernet dongle was used. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved Modbus Client sending zero value when Holding Register was not zero. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved screen calibration corruption when data was being written beyond 128 words (%M2048) that was using the Write removable media block. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved the following issues: • UTC time not being updated when downloaded from Cscape.
• Default audio volume was too low when compared with previous firmware versions.
Note: UTC time will not be updated when downloaded from Cscape using IEC/Enhanced IEC language. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved CAN2 stops working after several power cycles. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved possible condition where device could get stuck on splash screen after several power cycles. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved %SR181 and %SR182 not updating for Unacknowledged and Active alarms. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved an unintended condition in which the display could be kept on by a mini-USB connection even when 24V supply to the controller was removed. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved title bar of password object showing nonsense when Unicode fonts were created. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved WebMI alarm history page not listing the RTN alarms. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved CANOpen blocks not working when CAN1 port was configured as CANOpen and CAN2 port as J1939. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.32 | April 2024 | Bug Fix | Resolved ASCII string on the Allen Bradley PLC was being corrupted when second ASCII string was being transferred from controller. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Enhancement | Added new OCSIO modules - DQM606, DIM610 and CNX100; NOTE: CNX100 requires Cscape 9.90 SP10 onwards | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Enhancement | Added new system registers for storing PGM password (%SR104 and %SR106) in order to avoid opening of password dialog when PGM is loaded via SR bits. (8345) NOTE: This requires Cscape 9.90 SP9 onwards. %SR104 – 32bit %SR for storing password of program which is currently running.%SR106 – 32bit %SR for storing password of program which is being loaded | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Enhancement | Added Ethernet dongle status register - %S15 (10185) NOTE: When the Ethernet dongle is connected, %S15 bit will be enabled, once it is removed, %S15 bit will be disabled. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Enhancement | Feature request to add a reset bit for EtherNet/IP Server. (8633) NOTE: SR156.3 for Ethernet/Ip protocol Lan1 reset. SR153.3 for Ethernet/Ip protocol Lan2 reset. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein user was not able to access files in a folder when FTP was configured as Read Only (10040) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein MQTT NBIRTH/NDEATH packets were causing loss of communications (8642) NOTE: This requires Cscape 9.90 SP9 onwards. Added bdsequence number to the birth message packets. | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Added time zone information in email header to avoid email sent from OCS being treated as spams (9105) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein unit was not showing negative value when CPU temperature was below Zero deg C and min/max value would wrap around (8587) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein only limited number of users configured in user security configuration was working (10016) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein device would PING for an invalid subnet mask configured (8765) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.30 | July 2023 | Bug Fix | Resolved issue wherein unplugging and plugging LAN cable from ETX200 base was not resuming communication on their own and required device restart to resume communications (8635) | Bootloader, Cscape 9.90 SP9 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.28 | May 2023 | Bug Fix | Resolved issue when the X5 Prime was reporting bad clock/battery and would sometimes default the clock. (9903) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.28 | May 2023 | Bug Fix | Resolved issue where audio was not functional when 105 IO card was being used on XL7/XL10 Prime models. This also solves slow boot issue. (7530) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.22 | March 2023 | Bug Fix | Resolved issue where XL Prime units could drop out of RUN mode due to a logic error. (9527) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.20 | March 2023 | Enhancement | OCSIO Support has been added. This requires Cscape 9.90 SP8 onwards. | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.20 | March 2023 | Enhancement | Improved upgrade procedure for non-bootable microSD card option. | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.20 | March 2023 | Enhancement | Added "Replace System Graphics" support in System recovery screen for customizing slide key* and splash screen. *Slide key customization applicable to XLW Prime and X5 Prime only. | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.20 | March 2023 | Bug Fix | Resolved touch and bootup issue at low temperature. (8929) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.16 | October 2022 | Bug Fix | Fixed issue where incorrect data was being populated into the upper word for High Speed Counter inputs. (8706) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.14 | September 2022 | Enhancement | Support added for LAN2 when using included USB Dongle for XL7 and XL10 Prime models only. Requires Cscape 9.9 SP8 or higher. | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.14 | September 2022 | Enhancement | New X5 Prime model has been added. NOTE: Requires Cscape 9.90 SP8 or higher. | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.14 | September 2022 | Bug Fix | Resolved issue when conversion blocks were working for ODD register numbers only and was failing EVEN register number in Register-Based Advanced Ladder. (6233) | Bootloader, Cscape 9.90 SP8 or higher |
Prime XL4, XL6, XLW, XL7, XL10, X5 | CSCAN 16.14 | September 2022 | Bug Fix | Serial Modbus communication has been improved for higher baud rates. (7674) | Bootloader, Cscape 9.90 SP8 or higher |