Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: At times, some programs were becoming corrupted or losing graphics and the unit displayed “Invalid graphics” after power cycle. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: Device would freeze sometimes at “controller Fw-xx.xx.xxx" screen after power cycle. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: Canvas value of a PID block was not updating when configured in Enhanced IEC program. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: RTC time was being incremented by one (1) hour per power cycle when Daylight savings time was enabled. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: NTP server was skipping a day on New Year's Day if it was a leap year. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: Protocol size was displayed as +++++++ for BACNet MSTP server in System Menu | View Status. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.04 | August 2024 | Bug Fix | Resolved: Read RM block was reading entire elements / data for an ASCII data type instead of reading only the configured number of elements. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 10D only | 17.04 | August 2024 | Bug Fix | Resolved USB Type C communication not working on Canvas 10D model. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Added build version and firmware version in system menu | view status. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Added limitations for Enhanced IEC Removable media Write and Read blocks to resolve the screen calibration being corrupted / system exception was being obtained when data was being written beyond 128 words (%M2048) using write removable media block | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Added support for using external modem as client with modem blocks. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Resolved MAC ID was not being displayed in LAN2 when USB to ethernet dongle was used. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Resolved Modbus Client sending zero value when Holding Register was not zero. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Resolved screen calibration corruption when data was being written beyond 128 words (%M2048) that was using the Write removable media block. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Resolved the following issues: • UTC time not being updated when downloaded from Cscape. • Default audio volume was too low when compared with previous firmware versions. Note: UTC time will not be updated when downloaded from Cscape using IEC/Enhanced IEC language. | Bootloader, Cscape 9.90 SP9 or higher |
Canvas 4, 5, 7, 7D, 10D | 17.00 | July 2024 | Enhancement | Resolved CAN2 stops working after several power cycles. | Bootloader, Cscape 9.90 SP9 or higher |